1000A-40VACDC Dry Type Load Bank

1000A-40VACDC Dry Type Load Bank
Details:
This is a dry type pure resistive load bank. It can be equiped with universal wheels under the cabinet. Load bank capacity, voltage, power steps could be customized. It is used for electric load testing and maintenance purpose.
Send Inquiry
Download
Description
Technical Parameters

1000A 32-40VAC/DC Load Bank 


This is an indoor use pure resistive load bank. It can test AC and DC voltage from 32V to 40V, current 1000A. Max. Power 40KW. 


Parameters: 

Model

LB-1000A-40VAC/DC-J

Type

AC/DC resistive load

Testing Voltage

32~40VAC/DC

Rated Power

40kW40VAC/DC, 25.6kW32VAC/DC

Power Factor

1

Power Steps

50A,50A,100A,100A,100A,200A,200A,200A, total 8 steps, 1000A

Control Mode

Contactors( manual control)

Loading

Continuously adjustable

Power Frequency Withstand Voltage

AC1000V/50Hz 1min, no breakdown, no arcing

Insulation Resistance

≥10MΩ between the main circuit and the shell (DC1000V megger)

Protection & Alarm

Short Circuit, Fan Air Volume, High Temperature Fault(temperature adjustable)

Ingress Protection

IP20

Resistance Accuracy

≤±3%

Parameters Display

Voltage, Current, Power, Running Time

Control Function

Loads increase and decrease control, and sudden loading and unloading control

Dimension

900*800*1600 mm

Working Mode

Continuous

Insulation Grade

F

Cooling

Forced air cooling, air in from side, out from top

Accuracy

0.5

Working Power Supply

AC400V/50Hz

Service Location

Indoor

Weight

About 220KG


Control Method

Local manual panel control

The load bank has a control panel. Through the panel, user can control the loading and unloading of power and the operation of the fan. There are power steps indicators, fan indicators, temperature display in the resistance room on the panel, and E-Stop, sound and light alarm as well.


Protection System

(1) Emergency stop: All loads can be unloaded by press this button, and cannot be loaded in the locked state of emergency stop, and an audible and visual alarm will be issued.

(2) Short-circuit protection: The load circuit is equipped with a fuse, which is unloaded in the event of a short-circuit.

(3) Temperature protection: There is a temperature measuring instrument on the control panel of the load bank, which displays the temperature in the load box. When the temperature exceeds the safety threshold, loads will be unloaded and alarmed.

(4) Fan air volume protection: When the air volume of any fan is insufficient, loads will be automatically unloaded and alarm step by step.

(5) Fan thermal overload protection: when any fan fails to operate normally, loads will be automatically unloaded and alarm step by step.




 

Hot Tags: 1000a-40vacdc dry type load bank, China, manufacturers, suppliers, factory, customized, price, made in China